Catalogue Code: XPE1500 Keor XPE 1500 kW
  • Model
    Keor XPE
  • Rating
    1500 kW
  • Dimension (mm)
    6250 x 980 x 2100 (W x D x H)
  • Weight (kgs)
    5200
About the product

Keor XPE is a modular, scalable and flexible high-power UPS system. Based on its 250 kW or 300 kW power units, it can provide maximum nominal power of 2.1 MW. Its 3-level Inverter technology delivers up to 97% online efficiency which significantly helps reduce power loss and ensures less stress on each component. Its sustainable design not only offers considerable energy saving, but also has high recyclable rate. Keor XPE is PEP certified and is the ideal solution for large data centers and critical power applications where continuity of service, high-quality power supply and low consumption is a necessity.

Segments
  • Data Center
  • Manufacturing
  • Healthcare
Generic Features
  • Upto 97% efficiency on low load level
  • Modular & Scalable Architecture to grow as per business needs
  • Hot-Serviceable design to ensure maximum availability & uptime
  • Individual Logic & Control provides redundancy at each level
  • Top & Bottom Cable entry for ease of installation
  • Installation against the wall for ease of maintenance & troubleshooting
  • Flexible physical layouts to ensure optimized footprints
  • 10’’ Smart display for ease of use
General
  • Capacity: 1500 kW
  • Overall Efficiency: Upto 97%
  • Inverter Efficiency: Upto 96%
  • ECO Mode: Upto 99%
  • EMI / RFI Filter: Yes
  • Technology: On-line double conversion VFI-SS-111
  • Isolation Transformer: NA
  • IOBM Capacity: 1500 kVA
  • Power Units Power (kW): 300 kW
  • Number of Power Units: 5
  • Number of Power Units (IF N+1 Redundant): 5+1
  • Manual Bypass: Optional
Input Parameters
  • Input Voltage: 400 Vac + 3Ph + 4 Wire
  • Input Voltage Range: -20%, +15% (rectifier); ±10% (bypass)
  • Input Connection: 3W + N + G
  • Input Power Factor: > 0.99
  • THDi: <2%
  • Input Frequency Range: 50/60 Hz; range 45-65 Hz
DC Characteristics
  • Battery Connection: 3 wire (Distributed or Centralize)
  • Standard Charging Current: Yes
  • Max Charging Current: 200 Amps
  • Battery Type: VRLA/Lithium - ION/Nicd/Fly Wheel
  • Number of Batteries: 60-62 No's (12V VRLA)
Output Parameters
  • Output Connection: 3W + N
  • Output PF: Unity
  • Output Frequency: 50 /60 Hz (Adjustable)
  • Output Waveform Type: Sinewave
  • Overload Capacity 125%: 10 Min
  • Overload Capacity 150%: 1 Min
  • Output Frequency: 50/60 Hz
  • Output Voltage (in VAC): 380, 400, 415V (3Ph+N+PE)
  • Output frequency tolerance: ±0,1%Synch with Mains; ±0,01% Free Run
  • Crest Factor: up to 3:1
  • THD of output voltage: < 1% at full linear load
  • Output power factor: 0.7 leading to 0.5 lagging without derating
Protections
  • Ingress Protection: IP 20
  • Input Low / High Protection: Yes
  • Output Low / High Protection: Yes
  • Overload Protection: Yes
  • Short Circuit Protection: Yes
  • Surge Protection: Yes
Communication Options
  • MODBUS
  • SNMP
  • Dry Contacts
  • RS 232
  • Temperature
  • Humidity
  • Email Facility
Environment Features
  • Operating Temperature: 0 - 40 °C
Certificates
  • UE / CE Certificate
  • RoHS
  • PEP
Compliance
  • IEC 620 40 -1, IEC 620 40 - 2, IEC 620 40 -3
Physical Characteristics
  • Width (mm): 6250
  • Depth (mm): 980
  • Height (mm): 2100
  • Weight (kgs): 5200